  • Copper core PVC insulated copper tape shielded/PVC sheathed control cable
4/6

Copper core PVC insulated copper tape shielded/PVC sheathed control cable

Suitable for control, monitoring circuits and protection lines with rated voltage of 450/750V and below, mainly used in places where electromagnetic wave interference is prevented and shielding is required. It is laid indoors, cable trenches, pipelines, direct burial and other fixed places that can withstand large mechanical tensile forces.
Add WeChat Add WeChat
Hotline:

+86-400 0399 550

Hotline:

+86-198 6500 9392

Get a quote Contact us

  • Features
  • Standard
  • Parameter
  • Others
structural characteristics

• Conductor: Copper conductor, divided into Class 1 single stranded conductor and Class 2 7-stranded conductor

• Insulation: PVC polyvinyl chloride

Electrical characteristics

• Rated voltage Uo/U: 450/750 V

Usage characteristics

• The maximum allowable long-term operating temperature for conductors is 70 ℃

• Maximum core temperature for short circuit (duration not exceeding 5 seconds): 160 ° C

• Operating temperature range: -20 ° C to 70 ° C

Installation features

• The ambient temperature during laying should not be lower than 0 ℃

• The bending radius during laying should not be less than 12 times the outer diameter of the cable

Applicable Standards:

GB9330-88 / IEC60227

Type: KVVP2

Conductor Material: Oxygen-free copper (Copper content: 99.99%)

Number of Cores: Multi-core

Insulation Material: PVC (Polyvinyl Chloride)

Rated Voltage: 450/750V

Max. Conductor Temperature: 105 ℃

Colors: Red, Yellow, Green, Blue, Black, Yellow-green

Type Product Name Number of Cable Cores Cross-section (mm²) Shield Suppression Factor
KVVP2 Copper Core PVC Insulated, Copper Tape Shielded, PVC Sheathed Control Cable 4~61 1, 1.5, 2.5 0.007
4~14 4, 6
4~10 10
Delivery Length Transportation
● Cables weighing less than 80kg may be delivered in coils. Each finished cable shall be at least 100m long, or supplied at any length agreed by both parties.
● Any delivery length is acceptable as per agreement
● Cables must be firmly fixed during transportation to prevent damage to cables or reels from collision or overturning.
● Avoid sharp bending and other mechanical damage. Cable reels shall not be laid flat.
● It is strictly forbidden to drop cable reels loaded with cables from heights during transit.
● Special lifting gear shall be used for cable hoisting. Horizontal lifting of reels or pushing cables down directly from height is prohibited.
Length Tolerance Storage
● The length measurement error shall not exceed ±0.5% ● Finished cables shall be stored at 0~40℃ with relative humidity below 85%. Protect from direct sunlight and rain, provide proper ventilation and keep dry.
Packaging Installation Instructions
● Coiled or reeled cables shall be neatly wound and properly packed. Cable reels shall conform to JB/T 8137-1999.
● Cable ends shall be reliably sealed. Cable ends protruding from reels shall be fitted with protective covers, with projection length less than 300mm.
● A label shall be attached to each package showing:
a) Manufacturer’s name and trademark
b) Cable type and specification
c) Rated voltage
d) Length (m)
e) Weight (kg)
f) Date of manufacture
g) Standard number or certification mark
h) Symbol indicating correct rotation direction of cable reel
● Ambient temperature during installation shall not be lower than 0℃. If the measured temperature is below 0℃, preheat the cable before installation.
● The bending radius during cable laying must be strictly controlled to avoid internal mechanical damage.
● If man-made defects occur during laying (e.g. outer sheath damage), repair immediately or contact our after-sales department.