  • Copper core cross-linked polyethylene insulated polyvinyl chloride sheathed copper tape shielded control cable
4/6

Copper core cross-linked polyethylene insulated polyvinyl chloride sheathed copper tape shielded control cable

Suitable for connecting wires of control, monitoring circuits, and protection circuits with rated voltages of 450/750V and below, it has the characteristics of high mechanical strength, excellent electrical performance, and chemical corrosion resistance.
Add WeChat Add WeChat
Hotline:

+86-400 0399 550

Hotline:

+86-198 6500 9392

Get a quote Contact us

  • Features
  • Standard
  • Parameter
  • Others
structural characteristics

• Conductor: Copper conductor, divided into Class 1 single stranded conductor, Stranded Class 2 conductor, Stranded Class 5 conductor

• Insulation: XLPE cross-linked polyethylene

Electrical characteristics

• Rated voltage Uo/U: 450/750 V

Usage characteristics

• The maximum allowable long-term operating temperature for conductors is 90 ℃

• Maximum core temperature for short circuit (duration not exceeding 5 seconds): 250 ° C

• Operating temperature range: -20 to 90 ° C

Installation features

• The ambient temperature during laying should not be lower than 0 ℃

• The bending radius during laying should not be less than 12 times the outer diameter of the cable

Applicable Standards:

GB9330 / IEC60502

Type: KYJVP2

Conductor Material: Oxygen-free copper (Copper content: 99.99%)

Number of Cores: Multi-core

Insulation Material: XLPE (Cross-linked Polyethylene)

Rated Voltage: 450/750V

Max. Conductor Temperature: 90 ℃

Colors: Red, Yellow, Green, Blue, Black, Yellow-green

Type Product Name Number of Cable Cores Cross-section (mm²)
KYJVP2 Copper Core XLPE Insulated PVC Sheathed Copper Tape Shielded Control Cable 4~61 0.75, 1, 1.5, 2.5
4~14 4, 6
4~10 10
Delivery Length Transportation
● Cables weighing less than 80kg can be delivered in coils. Each finished cable shall be no less than 100m, or delivered at any length agreed by both parties.
● Any delivery length is acceptable upon agreement
● Cables shall be firmly fixed during transportation to avoid damage to cables or reels caused by collision or overturning.
● Prevent sharp bending and other mechanical damage. Cable reels shall not be placed flat.
● It is strictly prohibited to drop cable reels with cables from high places during transportation.
● Special lifting equipment shall be adopted for cable hoisting. Horizontal lifting of reels or pushing cables down directly from height is forbidden.
Length Tolerance Storage
● The length measurement error shall not exceed ±0.5% ● Finished cables shall be stored in an environment with temperature of 0~40℃ and humidity below 85%. Keep away from direct sunlight and rain, with proper ventilation to keep dry.
Packaging Installation Instructions
● Coiled or reeled cables shall be neatly wound and properly packed. Cable reels shall comply with JB/T 8137-1999.
● Cable ends shall be reliably sealed. Cable ends extending out of the reel shall be equipped with protective covers, and the extension length shall be less than 300mm.
● Labels shall be attached on cable packages indicating:
a) Manufacturer’s name and trademark
b) Cable type and specification
c) Rated voltage
d) Length (m)
e) Weight (kg)
f) Manufacturing date
g) Standard number or certification mark
h) Symbol for correct rotation direction of cable reel
● The ambient temperature during installation shall not be lower than 0℃. If the measured ambient temperature is below 0℃, preheat the cable before installation.
● The bending radius during cable laying shall be strictly controlled to prevent internal mechanical damage to the cable.
● If man-made quality issues occur during cable laying (such as outer sheath damage), repair it immediately or notify our after-sales service department.